GBV-120-385-1+1FM Single-Phase AC Power Surge Protective Device, Class II, 120kA Imax

Request a quote

Request a Quote

Description

The GBV-120-385-1+1FM is a Class II surge protective device (SPD) designed for lightning overvoltage protection of single-phase AC power supplies. It combines an L-N protection path and an N-PE protection path in one unit, with a nominal discharge current In of 60kA and a maximum discharge current Imax of 120kA.

Product Overview

The device is intended for Class II lightning overvoltage protection on single-phase AC power. It has a nominal operating voltage Un of 220V~, a maximum continuous operating voltage Uc of 385V~ for the L-N path, and a maximum continuous operating voltage Uc of 255V~ for the N-PE path. Voltage protection levels are 3.0kV for L-N and 2.0kV for N-PE, both measured at In with an 8/20µs waveform.

Key Features

  • Class II SPD for single-phase AC power
  • Combined L-N and N-PE protection in one unit
  • Nominal discharge current In: 60kA; maximum discharge current Imax: 120kA
  • Status indicator window: white for normal operation, red for failure
  • Changeover remote-signalling contact, NC-COM normally closed
  • 35mm DIN rail mounting
  • PBT housing with UL94-V0 flame rating and IP20 enclosure protection

Technical Specifications

Parameter Value
SPD classification II
Nominal operating voltage Un 220V~
L-N maximum continuous operating voltage Uc 385V~
N-PE maximum continuous operating voltage Uc 255V~
Nominal discharge current In 60kA
Maximum discharge current Imax 120kA
L-N voltage protection level Up (In @ 8/20µs) 3.0kV
N-PE voltage protection level Up (In @ 8/20µs) 2.0kV
L-N response time tA 25ns
N-PE response time tA 100ns
L-N and N-PE status indication White: normal / Red: failed
Mounting 35mm DIN rail
Conductor connection capacity ≤35mm²
Maximum torque 3.5Nm~4.5Nm
Housing material PBT
Housing flame rating UL94-V0
Enclosure protection rating IP20
Remote-signalling contact type Changeover contact, NC-COM normally closed
Remote-signalling contact AC rating 250V/0.5A
Remote-signalling contact DC rating 125V/0.2A
Remote-signalling contact terminal conductor capacity ≤1.5mm²
Temperature and humidity range -40℃ to +80℃, relative humidity ≤95%
Altitude ≤3000m
Main body dimensions 90mm×65mm×54mm

Applications

The GBV-120-385-1+1FM is used for Class II lightning overvoltage protection of single-phase AC power supplies. It is suitable for installation at distribution points where a single-phase AC supply requires L-N and N-PE surge protection.

Installation and Use

The device can be connected using conventional direct parallel wiring or V-shaped wiring. For better protection with direct parallel wiring, keep the connection conductors as short as possible, with a total length within 0.5m. Use 25-35mm² multi-core copper conductors for the main connections.

A suitable air circuit breaker or fuse must be connected in series ahead of the SPD; the circuit breaker should have a C trip characteristic. The power supply must be disconnected during installation; live operation is strictly prohibited, and the connecting conductors must meet the specified requirements.

During normal operation, the status indicator window is white and the alarm dry contact NC-COM is in the conducting state. When the SPD fails, the status indicator turns red and the NC-COM alarm dry contact changes to the open state. The SPD requires no special maintenance; periodically check whether the module is loose and whether the status indication is normal.

The SPD should be replaced promptly if either of the following occurs: the status indicator turns red, or the alarm dry contact changes to the open state.

Frequently Asked Questions

What does the status indicator window show?

The window is white during normal operation and turns red when the SPD has failed.

How does the remote-signalling contact behave?

The changeover contact NC-COM is normally closed and conducting during normal operation. It changes to the open state when the SPD fails.

What conductor size is required for the main connections?

Use 25-35mm² multi-core copper conductors. The terminal connection capacity is ≤35mm², and the maximum torque is 3.5Nm~4.5Nm.