TÜV Rheinland Certificate of Conformity — Surge Protective Device

Overview

This document is a Certificate of Conformity issued by TÜV Rheinland LGA Products GmbH under the Low Voltage Directive (EU) 2014/35. It is based on an evaluation of a sample of the product identified as a Surge Protector (Surge Protective Device).

The certificate states that the tested sample conforms with Annex I of Council Directive (EU) 2014/35. It also notes that the certificate does not imply assessment of series production and does not permit use of a TÜV Rheinland mark of conformity. The holder is authorized to use the certificate in connection with the EC declaration of conformity according to Annex IV of the Directive.

What this document covers

The certificate covers a Surge Protector (Surge Protective Device) sample with the following type designations:

  • G1V-80/385/B+C/a FM
  • G1V-80/385/B+C/b+1 FM

Where a = 1, 2, 3 or 4 and b = 1 or 3. The serial number is listed as an engineering sample. Testing is stated as according to EN 61643-11:2012+A11.

Key facts table

Item Detail
Registration No. AN 50663316 0001
Report No. CN25SYRL 001
Holder Guangdong Guard Group Co., Ltd.
Product Surge Protector (Surge Protective Device)
Issuer TÜV Rheinland LGA Products GmbH
Date 2025-02-24
Directive Low Voltage Directive (EU) 2014/35, Annex I
Test standard EN 61643-11:2012+A11
Uc 1) 385 V AC (L/N-PE); 2) 385 V AC (L-N), 255 V AC (N-PE)
In 40 kA
Imax 80 kA
Up 1) 1.8 kV (L/N-PE); 2) 1.8 kV (L-N), 1.6 kV (N-PE)
Isccr 300 A
Type of SPD Type 2
IP code IP20
Location Indoor
Number of ports One port
Temperatures -40°C ~ +80°C

How to use it

This certificate can be referenced in connection with the EC declaration of conformity according to Annex IV of the Low Voltage Directive. It applies to the evaluated sample and the listed type designations only. Because the certificate does not imply assessment of series production, it should not be presented as covering all manufactured units. The CE marking may be used if all relevant and effective EC Directives and Regulations are complied with.