Overview
This document is a Certificate of Conformity issued by TÜV Rheinland LGA Products GmbH under the Low Voltage Directive (EU) 2014/35. It is based on an evaluation of a sample of the product identified as a Surge Protector (Surge Protective Device).
The certificate states that the tested sample conforms with Annex I of Council Directive (EU) 2014/35. It also notes that the certificate does not imply assessment of series production and does not permit use of a TÜV Rheinland mark of conformity. The holder is authorized to use the certificate in connection with the EC declaration of conformity according to Annex IV of the Directive.
What this document covers
The certificate covers a Surge Protector (Surge Protective Device) sample with the following type designations:
- G1V-80/385/B+C/a FM
- G1V-80/385/B+C/b+1 FM
Where a = 1, 2, 3 or 4 and b = 1 or 3. The serial number is listed as an engineering sample. Testing is stated as according to EN 61643-11:2012+A11.
Key facts table
| Item | Detail |
|---|---|
| Registration No. | AN 50663316 0001 |
| Report No. | CN25SYRL 001 |
| Holder | Guangdong Guard Group Co., Ltd. |
| Product | Surge Protector (Surge Protective Device) |
| Issuer | TÜV Rheinland LGA Products GmbH |
| Date | 2025-02-24 |
| Directive | Low Voltage Directive (EU) 2014/35, Annex I |
| Test standard | EN 61643-11:2012+A11 |
| Uc | 1) 385 V AC (L/N-PE); 2) 385 V AC (L-N), 255 V AC (N-PE) |
| In | 40 kA |
| Imax | 80 kA |
| Up | 1) 1.8 kV (L/N-PE); 2) 1.8 kV (L-N), 1.6 kV (N-PE) |
| Isccr | 300 A |
| Type of SPD | Type 2 |
| IP code | IP20 |
| Location | Indoor |
| Number of ports | One port |
| Temperatures | -40°C ~ +80°C |
How to use it
This certificate can be referenced in connection with the EC declaration of conformity according to Annex IV of the Low Voltage Directive. It applies to the evaluated sample and the listed type designations only. Because the certificate does not imply assessment of series production, it should not be presented as covering all manufactured units. The CE marking may be used if all relevant and effective EC Directives and Regulations are complied with.