GDE-32A1P-lgt-20GB10A+4GB16A-FT-A Rack PDU, 32A 1P Input, 20× GB10A + 4× GB16A Anti-Loosening Outlets
Request a quote
Description
The GDE-32A1P-lgt-20GB10A+4GB16A-FT-A is a rack power distribution unit (PDU) rated for a single-phase AC220V 32A input. It distributes power to 24 outlets in a 20 + 4 combination: 20 GB10A anti-loosening outlets and 4 GB16A anti-loosening outlets. Power is brought in through a terminal box with a transparent cover, and the cable enters at the upper end of the unit.
Product Overview
The PDU is built around a copper bar internal connection of 2.5 mm diameter and is housed in a black RAL9005 aluminum alloy enclosure. A Schneider 32A/1P circuit breaker provides the air-switch protection function, and a hot-swap indicator light provides control indication. The unit is mounted by brackets in a vertical left orientation on the rear side of a cabinet.
Key Features
- Single-phase AC220V 32A input with a 20 + 4 outlet combination
- 20 GB10A anti-loosening outlets and 4 GB16A anti-loosening outlets
- Internal copper bar connection, 2.5 mm diameter
- Terminal box input with transparent cover; upper-end cable entry
- Schneider 32A/1P circuit breaker
- Hot-swap indicator light
- Black RAL9005 aluminum alloy housing
- Bracket mounting, vertical left orientation (rear side of cabinet)
Technical Specifications
| Parameter | Value |
|---|---|
| Product code | 10300363 |
| Product model | GDE-32A1P-lgt-20GB10A+4GB16A-FT-A |
| Product code (factory) | 051601501200 |
| Outlet types and quantity | 20 × GB10A + 4 × GB16A anti-loosening |
| Outlet combination | 20 + 4 |
| Internal connection | Copper bar connection (diameter 2.5 mm) |
| Power input method | Terminal box (transparent cover) |
| Cable plug type | / |
| Input connectable conductor capacity | 3 × 6 mm² |
| Cable installation method | Upper-end input |
| Cable fixing | PG19 |
| Circuit breaker brand | Schneider 32A/1P |
| Housing color | Black RAL9005 |
| Dimensions (L × W × H) | 1691 × 60 × 44 mm; tolerance: (L) ± 4 mm, (W/H) ± 2 mm |
| Fixing hole center distance | 1651 mm |
| Aluminum alloy housing length | 1591 mm |
| Installation method | Bracket mounting |
| Bracket installation direction | Vertical left installation (rear side of cabinet) |
| Control indication function | Hot-swap indicator light |
| Protection monitoring function | Air switch |
| Screw torque | M3: 0.6 N·m / 6 kgf·cm; M4: 1.6 N·m / 16.3 kgf·cm; M5: 3 N·m / 30.5 kgf·cm; M6: 5 N·m / 51 kgf·cm; M8: 11 N·m / 112 kgf·cm (torque ±10%) |
| Factory accessories | M6 × 12 screws and M6 floating square nuts, 4 pcs each; manual (including certificate of conformity) 1 pcs |
| Product identification — input | AC220V 32A |
| Product identification — output | 20 × GB10A + 4 × GB16A anti-loosening |
| Warranty period | 3 years |
Applications
The GDE-32A1P-lgt-20GB10A+4GB16A-FT-A is intended for rack power distribution where a single-phase AC220V 32A feed must be divided across GB10A and GB16A anti-loosening outlets. Its vertical left bracket mounting on the rear side of a cabinet suits installation inside equipment cabinets.
Installation and Use
Input wiring is connected through the terminal box with transparent cover, with the cable entering at the upper end. The input accepts conductors of 3 × 6 mm², and the cable is fixed with a PG19 gland. The unit is mounted using brackets in a vertical left orientation on the rear side of the cabinet; the fixing hole center distance is 1651 mm.
When tightening screws, observe the specified torque values with a tolerance of ±10%: M3 at 0.6 N·m (6 kgf·cm), M4 at 1.6 N·m (16.3 kgf·cm), M5 at 3 N·m (30.5 kgf·cm), M6 at 5 N·m (51 kgf·cm), and M8 at 11 N·m (112 kgf·cm). Factory accessories include M6 × 12 screws and M6 floating square nuts (4 pcs each) and one manual including the certificate of conformity.
Frequently Asked Questions
What is the input rating of this PDU?
The input is rated AC220V 32A, single-phase, as marked on the product identification label.
How many outlets does the PDU provide?
It provides 24 outlets in total: 20 GB10A anti-loosening outlets and 4 GB16A anti-loosening outlets.
What is the mounting orientation?
The unit is bracket-mounted in a vertical left orientation on the rear side of the cabinet, with a fixing hole center distance of 1651 mm.
What conductor size does the input accept?
The input accepts 3 × 6 mm² conductors, connected through the terminal box with transparent cover and fixed with a PG19 gland.
Related products
-

PDU-AC380V-32A-21C13+6C19-GDE-32A-lgt-21C13+6C19-FT Rack Power Distribution Unit, AC380V 32A, 21×C13 + 6×C19 Anti-Loose Outlets
Request a quote -

PDU-AC220V-40A-16GB10A+4GB16A Rack PDU — 16× GB10A + 4× GB16A Anti-Drop Outlets, Vertical Left Mount
Request a quote -

GDE-32A-4 Rack PDU — 4-Way German Standard 16A Outlets, Horizontal Mount, AC220V 32A Input
Request a quote -

PDU-AC380V-32A3P-F-M-SPD-12GB10A+12GB16A-A-GDE Rack PDU, 12× GB10A + 12× GB16A Anti-Loose Outlets
Request a quote































Reviews
There are no reviews yet.