GCV-60-385-3+1-FM Three-Phase AC Power SPD, Class II, 60 kA with Remote Signaling

Request a quote

Request a Quote

Description

The GCV-60-385-3+1-FM is a Class II surge protective device (SPD) designed for lightning overvoltage protection of three-phase AC power supplies. It combines L-N and N-PE protection paths in one unit, with a nominal discharge current In of 30 kA and a maximum discharge current Imax of 60 kA.

Product Overview

The SPD is classified as Class II and is intended for overvoltage protection on three-phase AC power systems. It has a nominal operating voltage Un of 220 VAC, a maximum continuous operating voltage Uc of 385 VAC for the L-N path, and a maximum continuous operating voltage Uc of 255 VAC for the N-PE path. Voltage protection levels are 2.0 kV for L-N and 1.5 kV for N-PE, both measured at In with an 8/20 µs waveform.

Key Features

  • Class II three-phase AC power SPD with L-N and N-PE protection
  • Nominal discharge current In: 30 kA; maximum discharge current Imax: 60 kA
  • L-N voltage protection level Up: 2.0 kV; N-PE voltage protection level Up: 1.5 kV (In @ 8/20 µs)
  • Response time tA: 25 ns for L-N and 100 ns for N-PE
  • Status indication window: green for normal operation, red for failure
  • Changeover remote signaling contact: NC-COM-NO, with NC-COM normally closed and NO-COM normally open
  • 35 mm DIN rail mounting
  • Housing material flame-retardant rating: UL94-V0
  • Housing protection rating: IP20

Technical Specifications

Parameter Value
Model GCV-60/385/3+1 FM
SPD classification Class II
Nominal operating voltage Un 220 VAC
L-N maximum continuous operating voltage Uc 385 VAC
N-PE maximum continuous operating voltage Uc 255 VAC
Nominal discharge current In 30 kA
Maximum discharge current Imax 60 kA
L-N voltage protection level Up (In @ 8/20 µs) 2.0 kV
N-PE voltage protection level Up (In @ 8/20 µs) 1.5 kV
L-N response time tA 25 ns
N-PE response time tA 100 ns
L-N, N-PE status indication Green: normal / Red: failed
Mounting method 35 mm DIN rail
Conductor connection capacity ≤25 mm²
Maximum torque 3.2 Nm to 3.7 Nm
Housing material flame-retardant rating UL94-V0
Housing protection rating IP20
Remote signaling contact type Changeover contact, NC-COM-NO; NC-COM normally closed, NO-COM normally open
Remote signaling contact AC rating 250 V / 0.1 A
Remote signaling contact DC rating 30 V / 0.1 A
Remote signaling contact terminal conductor capacity ≤1.5 mm²
Temperature and humidity range -40 °C to +80 °C, relative humidity ≤95%
Altitude ≤4000 m
Environmental requirement RoHS compliant
Main body dimensions 90 mm × 65 mm × 72 mm (tolerance ±1 mm)

Applications

The GCV-60-385-3+1-FM is used for Class II lightning overvoltage protection of three-phase AC power supplies. It is suitable for installation in AC power distribution systems where L-N and N-PE surge protection is required.

Installation and Use

The SPD can be connected in the conventional direct parallel wiring mode or in a V-shaped wiring mode. For better protection performance with direct parallel wiring, keep the wiring as short as possible, with a total length within 0.5 m. Use 10-25 mm² multi-core copper conductors for the connection.

A suitable circuit breaker or fuse must be connected upstream of the SPD. The circuit breaker should have a C trip characteristic. The power supply must be disconnected during installation; live operation is strictly prohibited, and the connecting conductors must meet the specified requirements.

When the SPD is operating normally, the status indication window is green, the alarm dry contact NC-COM is conducting, and the alarm dry contact NO-COM is open. When the SPD has failed, the status indication turns red, the alarm dry contact NC-COM becomes open, and the alarm dry contact NO-COM becomes conducting.

The SPD requires no special maintenance. Periodically check whether the module is loose and whether the status indication is normal. The SPD is considered failed and should be replaced promptly if either of the following occurs: the status indication turns red, or the alarm dry contact becomes open.

Frequently Asked Questions

What does the status indication window show?

Green indicates normal operation, and red indicates that the SPD has failed.

How are the remote signaling contacts configured?

The SPD uses a changeover contact set NC-COM-NO. NC-COM is normally closed and NO-COM is normally open. When the SPD fails, NC-COM becomes open and NO-COM becomes conducting.

What conductor size is required for the main connections?

Use 10-25 mm² multi-core copper conductors. The terminal connection capacity is ≤25 mm², and the maximum torque is 3.2 Nm to 3.7 Nm.

What upstream protection is required?

A suitable circuit breaker or fuse must be connected upstream of the SPD, and the circuit breaker should have a C trip characteristic.