PDU-AC380V-32A3P-F-M-SPD-12GB10A+12GB16A-A-GDE Rack PDU, 12× GB10A + 12× GB16A Anti-Loose Outlets

Request a quote

Request a Quote

Description

The PDU-AC380V-32A3P-F-M-SPD-12GB10A+12GB16A-A-GDE is a rack power distribution unit rated for an AC380V 32A three-phase input. It distributes power through 12 GB10A and 12 GB16A anti-loose outlets, giving a total socket combination of 12+12. Internal connections use copper busbars of 2.5 mm diameter, and the enclosure is finished in black RAL9005.

Product Overview

This PDU is intended for cabinet power distribution where a three-phase AC380V 32A feed must be split across GB-standard 10A and 16A outlets. Input is made through a terminal block, with cable entry at the top and PG25 cable fixing. Protection and monitoring functions include a circuit breaker, a hot-swap digital meter, and an SPD. The unit mounts vertically on the left side at the rear of a cabinet using brackets.

Key Features

  • AC380V 32A three-phase input with terminal-block connection
  • 24 outlets total: 12 GB10A and 12 GB16A anti-loose sockets
  • Copper busbar internal connection, 2.5 mm diameter
  • Schneider 32A/3P circuit breaker
  • Hot-swap digital meter and hot-swap indicator lamp
  • SPD protection monitoring
  • Top cable entry with PG25 cable fixing
  • Black RAL9005 sheet-metal enclosure
  • Vertical left-side bracket mounting for the rear of a cabinet

Technical Specifications

Parameter Value
Product code 10300375
Product specification model GDE-32A3P-12GB10A+12GB16A-FT-A
Product code (internal) 051601501299
Input rating AC380V 32A
Phase and pole configuration 3P
Outlet type and quantity 12 × GB10A + 12 × GB16A anti-loose
Outlet combination 12+12
Internal connection Copper busbar, 2.5 mm diameter
Power input method Terminal block
Cable plug type Not applicable
Input conductor capacity 5 × 6 mm²
Cable installation method Top entry
Cable fixing PG25
Enclosure color Black RAL9005
Dimensions (L × W × H) 1610 × 100 × 45 mm
Dimension tolerance L ± 4 mm; W/H ± 2 mm
Mounting hole center distance 1575 mm
Sheet-metal enclosure length 1530 mm
Installation method Bracket mounting
Mounting direction Vertical left installation (rear of cabinet)
Control and indication Hot-swap indicator lamp
Protection and monitoring Circuit breaker, hot-swap digital meter, SPD
Circuit breaker brand and rating Schneider 32A/3P
Screw torque M3 0.6 N·m / 6 kgf·cm
Screw torque M4 1.6 N·m / 16.3 kgf·cm
Screw torque M5 3 N·m / 30.5 kgf·cm
Screw torque M6 5 N·m / 51 kgf·cm
Screw torque M8 11 N·m / 112 kgf·cm
Factory accessories M6×12 screws and M6 floating square nuts, 4 pcs each; manual with certificate of conformity, 1 pcs
Product identification model ZXSPDU-32A3P
Product identification input AC380V 32A
Product identification output 12 × GB10A + 12 × GB16A anti-loose
Warranty period 3 years

Applications

This PDU is used for power distribution inside equipment cabinets, where a three-phase AC380V 32A supply is distributed to GB10A and GB16A loads. Its vertical left-side rear-cabinet mounting and top cable entry suit rack installations that require a long, narrow distribution strip with integrated circuit-breaker, metering, and SPD monitoring functions.

Installation and Use

Install the PDU vertically on the left side at the rear of the cabinet using the supplied brackets. Route the input cable to the top entry point and secure it with the PG25 cable fixing. Connect the input conductors to the terminal block; the input conductor capacity is 5 × 6 mm². The unit accepts an AC380V 32A three-phase feed and is protected by a Schneider 32A/3P circuit breaker.

Use the specified screw torque values during assembly: M3 at 0.6 N·m (6 kgf·cm), M4 at 1.6 N·m (16.3 kgf·cm), M5 at 3 N·m (30.5 kgf·cm), M6 at 5 N·m (51 kgf·cm), and M8 at 11 N·m (112 kgf·cm). The factory accessory set includes M6×12 screws and M6 floating square nuts, 4 pcs each, plus one manual containing the certificate of conformity.

Frequently Asked Questions

What input rating does this PDU require?

The unit is rated for an AC380V 32A three-phase input and connects through a terminal block.

How many outlets does the PDU provide?

It provides 24 outlets in total: 12 GB10A anti-loose sockets and 12 GB16A anti-loose sockets.

What protection and monitoring functions are included?

The PDU includes a Schneider 32A/3P circuit breaker, a hot-swap digital meter, and an SPD, together with a hot-swap indicator lamp.

How is the unit mounted?

It is bracket-mounted vertically on the left side at the rear of the cabinet, with a mounting hole center distance of 1575 mm.

Reviews

There are no reviews yet.

Be the first to review “PDU-AC380V-32A3P-F-M-SPD-12GB10A+12GB16A-A-GDE Rack PDU, 12× GB10A + 12× GB16A Anti-Loose Outlets”